Chapter 2 Installing the Sun Fire X4150 Server Into a Rack with Slide-Rails 17
8. If available, extend the anti-tip foot at the bottom of the rack. (See FIGURE 2-5.)
FIGURE 2-5 Extending the Anti-tip Foot
Caution If your rack does not have an anti-tip foot, the rack could tip over.
Attaching Tool-less Slide-Rail Assemblies
To attach tool-less slide-rail assemblies to the rack, refer to the install card
instructions included with the kit.
Installing the Server Into the Slide-Rail
Assemblies
Use this procedure to install the server chassis, with mounting-brackets, into the
slide-rail assemblies that are mounted to the rack.
Caution This procedure requires a minimum of two
people because of the weight of the server. Attempting this
procedure alone could result in equipment damage or
personal injury.